What is a Motor Service Factor?
Motor service factor (SF) is the percentage multiplier that a motor can handle for short periods of time when operating within its normal voltage and frequency tolerance. In other words, it is a fudge factor that give extra horsepower when it's occasionally needed.
For instance, this 1/2 horsepower shown in the photo has a service factor of 1.25 so it can actually output 25% more power required for short periods of time. This comes in handy if the density of the liquid increases or a higher than normal flow rate is required.
Fractional horsepower motors usually have a higher service factor up to 1.5 since their power consumption does not lead to significantly higher winding temperatures. Motors of 10 hp and up usually have a service factor of 1.15.
The Canadian Electrical Code defines service factor as a multiplier that, when applied to:
The rated horsepower of an AC motor,
To the rated armature current of a DC motor, or
To the rated output of a generator,
... indicates a permissible loading that may be carried continuously at rated voltage and frequency. Note how the CEC allows for continuous operation while we reserve it for only short periods of time to ensure reliability.
As electrical consultants, using the service factor gives us a margin of safety that allows our design to:
Extend the life of the motor by lowering the temperature of the insulation winding.
Compensate for low or unbalanced supply voltages.
Accommodate the variability in horsepower. A 15% buffer is a nice margin to have especially for those occasional overload conditions.
Why Have a Service Factor
Operating a motor at its limit makes it more prone to overheating. A service factor allows the motor to operate below its theoretical maximum so it can run continuously with a cooler winding temperature at rated load. This leads to a longer life and better reliability.
Designing with the Service Factor
We never design systems to operate continuously at the maximum level (redundancy is a different topic). It is good practice to size a motor for continuously operation that is below the service factor percentage. An Electrical load monitoring test help to see how efficient a motor is running.
Operating in the service factor area may result in:
Decreased efficiency (more energy usage).
Decreased power factor (more reactive power usage).
Overheating and damage to the wire insulation.
Incorrect starter sizing which may lead to inadequate starting & pull-out torques.
A motor services factor is a margin of safety which increases the reliability of building systems.
Fractional horsepower motors usually have a higher service factor up to 1.5 since their power consumption does not lead to significantly higher winding temperatures. Motors of 10 hp and up usually have a service factor of 1.15.
The Canadian Electrical Code defines service factor as a multiplier that, when applied to:
The rated horsepower of an AC motor,
To the rated armature current of a DC motor, or
To the rated output of a generator,
... indicates a permissible loading that may be carried continuously at rated voltage and frequency. Note how the CEC allows for continuous operation while we reserve it for only short periods of time to ensure reliability.
As electrical consultants, using the service factor gives us a margin of safety that allows our design to:
Extend the life of the motor by lowering the temperature of the insulation winding.
Compensate for low or unbalanced supply voltages.
Accommodate the variability in horsepower. A 15% buffer is a nice margin to have especially for those occasional overload conditions.
Why Have a Service Factor
Operating a motor at its limit makes it more prone to overheating. A service factor allows the motor to operate below its theoretical maximum so it can run continuously with a cooler winding temperature at rated load. This leads to a longer life and better reliability.
Designing with the Service Factor
We never design systems to operate continuously at the maximum level (redundancy is a different topic). It is good practice to size a motor for continuously operation that is below the service factor percentage. An Electrical load monitoring test help to see how efficient a motor is running.
Operating in the service factor area may result in:
Decreased efficiency (more energy usage).
Decreased power factor (more reactive power usage).
Overheating and damage to the wire insulation.
Incorrect starter sizing which may lead to inadequate starting & pull-out torques.
A motor services factor is a margin of safety which increases the reliability of building systems.
Key: Vertical 3 Phase ac induction motors, electric motor, Vertical Inverter Duty motor, DC Brake motor Oil Pressure Motor, helical gear motor, AC mini Induction DC gear motor, Gear reducer motor series, NMRV NRV worm reducer series, Worm reducer series, Horizontal Inverter duty, worm gear series, ac motor, vertical gearmotor, helical horizontal gearmotor, gear reduce motor, bevel gearmotor, motor service, cyclo gear motor, NMRV gear motor, worm reducer
Newer articles
- Planetary Speed Reducer Working Principle and Applications (05/11/2019)
- Factors to Consider in Cabling a Reliable VFD System (07/11/2019)
- What are the Benefits of using a Frequency Converter With an Electric Motor? (06/11/2019)
- Why use a frequency inverter along with an electric motor? (01/11/2019)
- AC Gear Motors: Leveraging Torque-Boosting Power (31/10/2019)
- All you need to know about gear motors and their components (01/11/2019)
- Gear Reduction. A familiar term to many, but what does it actually mean? (05/08/2019)
- Defining motor service factor (02/09/2019)
- Calculating Power Factor (05/09/2019)
- How to Select a Gearmotors (01/10/2019)
Older articles
- How to select the best type of gear reducer (31/01/2019)
- How do gearmotors impact reflected mass inertia from the load? (06/05/2019)
- What is Service Factor and How is it Used? (31/07/2019)
- What You Need to Know about "Service Factor" (31/07/2019)
- Worm Gears – Applications & Uses (31/07/2019)
- Brake Motors function (02/08/2019)
- Why use a gearbox with a stepper motor? (14/07/2019)
- What are DC Motors Usually Gear Motors (21/06/2019)
- 5 tips prior to designing the gear motors (22/06/2019)
- Benefits to Using Dolin gear motors (01/05/2019)
Join